Description
Air-to-water REVERSE CYCLE HEAT PUMP, complete with water pump, 100-litre buffer tank, condensing pressure control, 2 x compressors, 2 x capacity control steps.
Operating range from -5°C to +15°C
Standard working conditions:
COOLING mode
- water from 12°C to 7°C
- outside air 35°C
- cooling capacity 68 kW
- power consumption 22,4 kW
HEATING mode
- water from 40°C to 45°C
- outside air7°C DB – 6°C WB
- heating capacity 72 kW
- power consumption 24,3 kW
Data sheet
Water 12/7 - Performance Kw kw 68
Flow mc/h from 5 to 14